TTS General Settings

Configuration of TTS-1nce/TTS-2 Sequences is performed in the World Properties window under TTS Sequences.

General

Control Network Settings (LAN-1), has an IP address field that reports the current IP address for the selected TTS that is used for IP communications with the device. The TTS IP Configuration window can be used to set this value or it can be added in this field.

Nurse Call Communications Options

The TTS RS-232 port is able to be used to communicate directly with a Rauland Nurse call system.

Enable Nurse Call - When selected the nurse call functions will be available.
Note: For TTS-1nce units, this requires additional licensing permissions in order to function. A Nurse Call Service Licence Alarm will indicate if licensing is not enabled.

Default Voice - can be specified. There are 140 voices installed and available on the TTS-2.
Individual voice packages must be purchased and installed on the TTS-1nce. 

Nurse Call Serial Port Options Settings:

Details of supported Flow Control, RTS and CTS settings:

Rauland

TTS-1nce/TTS-2

Flow Control

RTS Use

CTS Use

Flow Control

RTS Enable

DTR Enable

RTSCTS

Any

Any

RTS

Not Available

True/False

 

 

Xon Xoff

Any

Ignore

Xon/Xoff

True/False

True/False

Flow Control

True

True/False

Device Ready

True

True/False

 

 

Flow Off

Any

Ignore

None

True/False

True/False

Flow Control

True

True/False

Device Ready

True

True/False

 

 

DSR_DTR

Any

Ignore

None

True/False

True

Flow Control

True

True

Device Ready

True

True

 

 

DSR_DTR RTS

Any

Any

RTS

Not Available

True

None

True

True

RTS Xon/Xoff

Not Available

True

 

 

DSR_DTR_XON

Any

Ignore

Xon Xoff

True/False

True

Flow Control

True

True

Device Ready

True

True

 

Nurse Call Protocol - Rauland Responder 5 is supported.

Enable Passive Mode - Removes the monitoring of the RS-232 port if required. Please see the TTS RS-232 Wiring Topologies section for more details.

Enable Serial Communications Monitoring - This monitoring mechanism periodically checks the serial link between the Nurse Call System and the TTS. An alarm will be raised if the serial link is detected to be broken.

RS-232 Wiring
Please refer to the TTS RS-232 Wiring Topologies section for more details on the RS-232 interface connection to the TTS-2 or TTS-1nce. Note that the RS-232 port is disabled for the standard TTS-1e (non-Nurse Call).

Rauland Nurse Call Protocol options

Legacy Dial Back Pagers Disabled -

When Legacy Dial Back Pagers is disabled the TAP output format is: Area Description: Room Description: BedIndex

Example: If Area Description = CUBIC, Room Name = P1501, Bed Index = 1, and Call Priority = Patient

The TAP message would appear as: CUBICP1501:1 Patient

Area Field Width is user configurable depending on the settings in the Nurse Call system the TTS is interfacing to. For non-legacy systems a range between 1 and 5 is supported. These settings must match for correct operation.

Legacy Dial Back Pagers Enabled -

When Legacy Dial Back Pagers is enabled the TAP output format is: Area Dial Number*Room Dial Number*Bed Index

Example 1: If Area Dial Number = 15, Room Dial Number = 1501, Bed Index = 1 (with bed index 1 and 2 being the Patient Beds in the room) and Call Priority = Patient

The TAP message would appear as: 15*1501*1 Patient

Area Field Width is user configurable depending on the settings in the Nurse Call system the TTS-2 (or TTS-1nce) is interfacing to. For legacy systems the field is separated by a *. The length can be variable and longer than 5 characters. These settings must match for correct operation.

When disabled, TTS will not monitor the Serial Communications link. If the Passive Mode is enabled, the Serial Communications Monitoring will automatically disable.