LSI-16e Hardware

This section is provided to aid in the use of the LSI-16e. Please see the LSI-16e Manual for further information on installation of the device.

Front Panel

The LSI-16e features twenty-three LEDs on the front plate (from left to right):

(1) Power

The first LED on the left of the front panel indicates power status

1. Not illuminated: The device is not powered.

2. Solid green: The unit is operational. Power is being supplied from either the main or PoE supply.

(2) General Alarm

This LED will illuminate red if the LSI-16e receives an alarm signal from an external emergency detection system (e.g. a fire alarm system) via the Alarm inputs to the LSI-16e. This LED indicates the General Alarm state.

1.Solid red - The LSI-16e has received an alarm signal from an external emergency detection system (e.g. fire alarm system).

2.Flashing red - The LSI-16e has received a General Alarm silence from an external emergency detection system (e.g. fire alarm system).

(3) General Fault

This LED will illuminate in yellow if there is a Fault in the life safety announcement system connected to the LSI-16e that does not affect the possible delivery of an Emergency Message.

(4) Power Supply Fault

This LED will illuminate in yellow the LSI-16e is operating on a PoE supply but the main 24V supply fails or an external power supply fault is signaled to the LSI-16e.

(5) Protection Fault

This LED will illuminate yellow if a system amplifier channel fails and this failure does not prevent an emergency zone voice announcement. Note: failures that do affect Emergency Zone voice announcements will result in a System Fault.

(6) Path Fault

This LED will illuminate in yellow if a fault in the transmission path is detected. The path integrity is tested from microphone capsule to end of loudspeaker lines if optional Vocia End of Line Device 1 (ELD-1) units are fitted at the end of the loudspeaker lines. If a PLD device detects errors on the speaker line it will also report as a Path Fault.

(7) System Fault

This LED indicates the integrity of the system:

1. Flashing yellow -The unit has a fault that may prevent the reliable operation of life safety announcement functions.

2. Not illuminated -The unit is operational without any faults that may prevent reliable operation of life safety announcement functions.

Because it indicates a potentially serious condition, the presence of a System Fault extinguishes indicators for PSU, Path and Protection faults so as to focus attention on the primary fault. However, individual PSU, Path and Protection faults are still shown in the system software and signaled to individual Fault outputs as described below.

The LSI-16e will always power up in the system fault condition. Manual intervention is required to take the LSI-16e out of this condition. Note: this power up condition does not prevent Emergency Zone voice announcements provided that the system is operating reliably.

(8–23) Interface Module LEDs

The sixteen Interface LEDs located on the front panel of the LSI-16e have two modes of operation. If there aren’t any GPIO-1 units associated with the LSI-16e then the 16 LEDs will indicate Zone and Alarm state the rear inputs local to the LSI-16e. In this default mode LED indication will behave in the following manner;

If however the LSI-16e has been assigned indicators from the GPIO-1 in the LSI-16e GPIO-1 Indicators section then the sixteen LEDs will fulfill a different role. They can be used to summarize the inputs states and monitoring fault conditions of one or more (up to 5) GPIO-1's per LSI-16e LED indicator. Refer to the GPIO-1 Fault State Indication on an LSI-16e section for more detail on the behavior in this mode.

 

View of an LSI-16e rear panel


Rear Panel

Please refer to the LSI-16 manual for further details on any of the information below.

Network Connection

The LSI-16e has two RJ45 connectors located on the rear panel that enable redundant network wiring for connectivity and secondary power supply. If communication fails on either Ethernet port, the LSI-16e reports a fault. For this reason, both Ethernet ports must be connected to the Vocia network, and both should be supplied from a PoE source for auxiliary power.

The RJ45 connectors utilize standard Ethernet cabling to interface the LSI-16e to the Vocia system via a managed network switch.

The RJ45 connector provides two LEDs that indicate Ethernet link and network activity. An LED either side of the RJ-45 socket will illuminate to indicate PoE power is being received.

 

Left LED Right LED Description
None None No power or data connectivity.  Please check the Device power and  network connection.
Amber Flashing Green Link established and CobraNet activity detected; the unit is acting as a CobraNet performer.
Flashing Amber Flashing Green Link established and CobraNet activity detected; the unit is operating as a CobraNet conductor.
Off Flashing Green Failover connection standing by in case the Primary connection fails. By default will be the right Hand socket (Secondary).
Flashing Amber None CobraNet fault. Check cabling and configuration for errors.

 

Monitored Outputs

Two black five-position connectors are located next to the rotary switches. These are predominately used for Monitored Outputs to external lamps or sounders. Individual output channels are labeled 1 through 8 (see table below for connector assignments).  One connection is configured for use as both an input and an output (1) and one as an input (2). See the LSI-16e Installation Manual for wiring instructions.

Marking Function
Ground
1 Sounder Output/ Silence Input
2 System Fault Reset Input
3 Voice Alarm Active
4 General Fault
5 PSU Fault
6 Protection Fault
7 Path Fault
8 External Supply Over-voltage Monitor
10V 10 Volt Out

 

The Monitored Outputs will sink current (pull low) when active (see the Specifications section of the LSI-16e manual for more details).  The desired load (lamp, LED, etc.) must be connected between the output terminal and a positive voltage reference.

These outputs are monitored and can detect open- or short-circuits in external connections. This feature facilitates compliance with voice evacuation standards. A load must be connected between each output and the positive voltage source. If any output on terminals 1 through 8 is unused, the output must be connected through an external resistor to the positive side of the voltage source (either 10V Out or user-supplied external source).  The value of each resistor should be 22kΩ to ensure proper functionality. An internally derived 10V source is provided at the 10V Out terminal; however, the total current available from this pin is limited to 100mA. This voltage source may be used for external devices provided the total load is less than 100mA.  

For higher-current devices, a user-supplied external voltage source of up to 35V may be used, with the negative side connected to the pin. Due to monitoring constraints, it is impossible to use both the internal 10V source and an external source.  For monitoring purposes, the positive side of the voltage source (either 10V Out or user-supplied external source) must be connected to the External Supply Over-voltage Monitor (terminal 8), as well as supplying voltage to external devices.

For more information please see the LSI-16e User Manual.

Control Inputs

Two five-position plug-in barrier strip connectors provide control input connections.  Eight separate channels plus two ground pins are provided (see table below for connector assignments).  Control inputs are fully isolated from all connections in the LSI-16.

Marking Function
Ground
1 PSU Fault (contact closure indicates a PSU Fault)
2 Ethernet Fault
3 Voice Alarm Silence from CIE (common for all zones)
4 Voice Alarm Reset from CIE (common for all zones)
Ground
5 Emergency Detection System Alarm 1
6 Emergency Detection System Alarm 2
7 Emergency Detection System Alarm 3
8 Emergency Detection System Alarm 4

 

Input Activation Conditions

Control Inputs 1 and 2

To activate an input, it must be connected to an external circuit that returns to either of the two pins. The resistance of this circuit must be less than 4kΩ.

Control Inputs 3 to 8

These inputs must be permanently connected to an external circuit that returns to either of the two pins. The resistance of this circuit must be between 1kΩ and 4kΩ. To activate an input, pull the input to a voltage between 12 and 24V.

PSU Fault

This input may be derived from the primary 24V power supply to indicate to the LSI-16 if there is a fault in the power supply.

This may be required for standards compliance.

Ethernet Fault

This input can be derived from an Ethernet switch to monitor the Ethernet network connection between the LSI-16 and amplifier. This may be required for standards compliance.

Voice Alarm Silence from CIE (fire alarm system)

This input is a signal from the CIE (fire alarm system) that will mute Emergency Messages in all Emergency Zones.

Voice Alarm Reset from CIE (fire alarm system)

This input is a signal from the CIE (fire alarm system) that will reset Emergency Messages in all Emergency Zones.

Emergency Detection System Alarm

These four inputs are used to connect to the fire alarm control and indicating equipment (CIE) and notify the LSI-16e that an alarm has occurred in a particular Zone. Four such Zone inputs may be connected. Additional Zone inputs will be available through the GPIO-1. When an Alarm is detected, the Vocia system will enter Emergency Mode as configured for that input. During Emergency Mode, some or all of the Vocia system will cease normal operation and operate as programmed for the Emergency.

System Fault Relay Connection

This relay is activated when the LSI-16e is fully operational. It may be used for informing external devices about the LSI-16e’s operating conditions or sounding an alarm to indicate the LSI-16e is not functioning correctly.

RS-232

This port may be used for RS-232 communication with the LSI-16e using LSI-VTP

24V DC Connector and LED

This is the primary (main) power supply input for the LSI-16e and as such must be fed from a suitable source of 24V DC capable of 15 watts (625mA). The 24V DC supply has to be sourced separately. In typical installations, this supply will be provided from a power supply compliant with local norms and required standards (typically battery-backed). The adjacent LED indicates the presence of power.